6/13
Breadcrumb Field code Setting name Range, step
Default value
Date Value
Field settings table
Installer setting at variance with
default value
9.2.1 [E-05]
[E-06]
[E-07]
R/W (*3)
R/O (*4)
No DHW (*3)
EKHW, small volume (*3)
Integrated (*4)
EKHW, big volume (*3)
EKHWP (*3)
3rd party, small coil (*3)
3rd
9.2.2 [D-02] R/W
0: No DHW pump
1: Instant hot water
2: Disinfection
3: Circulation
4: Circulation and disinfection
9.2.4 [D-07] R/W (*3)
R/O (*4)
0: No
1: Yes
└─ Back up heater
9.3.1 [E-03] R/O
3: 6V (*1)
4: 9W
9.3.2 [5-0D] R/W (*1)
R/O (*2)
0: 230V, 1~ (*1)
1: 230V, 3~ (*1)
2: 400V
9.3.3 [4-0A] R/W 0: 1
1: 1/1+2
2: 1/2
3: 1/2 + 1/1+2 in emer
9.3.4 [6-03] R/W 0~10kW, step: 0,2kW
2kW (*1)
3kW
9.3.5 [6-04] R/W 0~10kW, step: 0,2kW
4kW (*1)
6kW
9.3.6 [5-00] R/W 0: No
1: Yes
9.3.7 [5-01] R/W -15~35°C, step: 1°C
0°C
9.3.8 [4-00] R/W 0: Disabled
1: Enabled
2: Onl
DHW
└─ Booster heater
9.4.1 [6-02] R/W 0~10kW, step: 0,2kW
3kW (*3)
0kW
9.4.3 [8-03] R/W 20~95 min, step: 5 min
50 min
9.4.4 [4-03] R/W 0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Le
└─ Emergency
9.5.1 [4-06] R/W 0: Manual
1: Automatic(normal SH/DHW ON)
2: Auto red SH/DHW ON
3: Auto red SH/DHW OFF
4: SH ON/DHW OFF
9.5.2 [7-06] R/W
0: Disabled
1: Enabled
└─ Balancing
9.6.1 [5-02] R/W
0: Disabled
1: Enabled
9.6.2 [5-03] R/W -15~35°C, step: 1°C
0°C
9.6.3 [5-04] R/W 0~20°C, step: 1°C
10°C
9.6.4 [8-02] R/W 0~10 hour, step: 0,5 hour
3 hour
9.6.5 [8-00] R/W
0~20 min, step 1 min
1 min
9.6.6 [8-01] R/W 5~95 min, step: 5 min
30 min
9.6.7 [8-04] R/W 0~95 min, step: 5 min
95 min
Installer settings
9.7 [4-04] R/O 0: Continuous pump operation
1: Non continuous pump operation
2: OFF
└─ Benefit kWh power supply
9.8.2 [D-00] R/W
0: None
1: BSH only
2: BUH only
3: All heaters
9.8.3 [D-05] R/W 0: Forced off
1: As normal
9.8.4 [D-01] R/W
0: No
1: Active open
2: Active closed
3: Smart
rid
9.8.6
0: No
1: Yes
9.8.7 Enable Room buffering
0: No
1: Yes
9.8.8
0~20 kW, step: 0,5 kW
2 kW
└─ Power consumption control
9.9.1 [4-08] R/W
0: No limitation
1: Continuous
2: Di
uts
9.9.2 [4-09] R/W 0: Current
1: Power
9.9.3 [5-05] R/W 0~50 A, step: 1 A
50
9.9.4 [5-05] R/W 0~50 A, step: 1 A
50
Domestic hot water
DHW pump
Solar
BUH type
Voltage
Configuration
Capacity step 1
Additional capacity step 2
Equilibrium: Deactivate backup heater (or external backup heat source in case of a
bivalent system) above the equilibrium temperature for space heating?
Equilibrium temperature
Operation
Capacity
BSH eco timer
Operation
Emergency
Space heating priority
Priority temperature
Compressor forced off
Offset BSH setpoint
Anti-recycle timer
Minimum running timer
Maximum running timer
Additional timer
Water pipe freeze prevention
Allow heater
Allow pump
Power consumption control
Type
Limit
Benefit kWh power supply
Allow electric heaters
Limit setting kW
Limit 1
4P655201-1 - 2021.09
(*1) *6V_(*2) *9W_(*3) EBB*_(*4) EBV*_
(*5) *X*_(*6) *H*_(*7) *11*_(*8) *16*_
(*9) *SU*_(*10) *18*_(*11) *23*