8 | Configuration
Installer reference guide
124
ERGA04~08DAV3(A) + EHBH/X04+08DA*V7
Daikin Altherma 3 R W
4P618958-1 – 2020.03
8.5 Settings menu
You can set additional settings using the main menu screen and its submenus. The
most important settings are presented here.
8.5.1 Malfunctioning
In case of a malfunction, or will appear on the home screen. To display the
error code, open the menu screen and go to [0] Malfunctioning. Press for
more information about the error.
Malfunctioning
Room
Operation
User profile
Main zone
8.5.2 Room
Setpoint screen
Control the room temperature of the main zone via setpoint screen [1] Room.
See "8.3.5Setpoint screen"[4113].
Schedule
Indicate if the room temperature is controlled according to a schedule or not.
# Code Description
[1.1] N/A Schedule:
▪ No: Room temperature is directly controlled by
the user.
▪ Yes: Room temperature is controlled by a
schedule and can be modified by the user.
Heating schedule
Applicable for all models.
Define a heating schedule of the room temperature in [1.2] Heating schedule .
See "8.3.7Schedule screen: Example"[4114].
Cooling schedule
Only applicable for reversible models.
Define a cooling schedule of the room temperature in [1.3] Cooling schedule.
See "8.3.7Schedule screen: Example"[4114].
Antifrost
Room frost protection [1.4] prevents the room from getting too cold. This setting
behaves differently depending on the set unit control method [2.9]. Perform
actions according to the table below.
Main zone unit control method [2.9] Description
Leaving water temperature control
([C‑07]=0)
Room frost protection is NOT guaranteed.