8 | Configuration
Installer reference guide
156
ERGA04~08DAV3(A) + EHBH/X04+08DA*V7
Daikin Altherma 3 R W
4P618958-1 – 2020.03
HP Heat pump. If heating up time by the heat pump takes too long,
auxiliary heating by the backup heater can take place
T
HP MAX
Maximum heat pump temperature at sensor in domestic hot water
tank
T
HP OFF
Heat pump OFF temperature (T
HP MAX
−[6-01])
T
HP ON
Heat pump ON temperature (T
HP OFF
−[6-00])
T
DHW
Domestic hot water temperature
T
U
User setpoint temperature (as set on the user interface)
t Time
INFORMATION
The maximum heat pump temperature depends on the ambient temperature. For
more information, see the operation range.
8.5.7 User settings
Language
# Code Description
[7.1] N/A Language
Time/date
# Code Description
[7.2] N/A Set the local time and date
INFORMATION
By default, daylight savings time is enabled and clock format is set to 24 hours. If you
want to change these settings, you can do this in the menu structure (User
settings > Time/date) once the unit is initialised.
Holiday
About holiday mode
During your holiday, you can use the holiday mode to deviate from your normal
schedules without having to change them. While holiday mode is active, space
heating/cooling operation and domestic hot water operation will be turned off.
Room frost protection and anti-legionella operation will remain active.
Typical workflow
Using holiday mode typically consists of the following stages:
1 Setting the starting date and ending date of your holiday.
2 Activating the holiday mode.
To check if holiday mode is activated and/or running
If is displayed on the home screen, holiday mode is active.