8 | Configuration
Installer reference guide
128
ERGA04~08DAV3(A) + EHBH/X04+08DA*V7
Daikin Altherma 3 R W
4P618958-1 – 2020.03
▪ In Weather dependent LWT setpoint mode, the scheduled actions consist of
desired shift actions, either preset or custom.
# Code Description
[2.1] N/A Schedule:
▪ 0: No
▪ 1: Yes
Heating schedule
Define a heating temperature schedule for the main zone via [2.2] Heating
schedule.
See "8.3.7Schedule screen: Example"[4114].
Cooling schedule
Define a cooling temperature schedule for the main zone via [2.3] Cooling
schedule.
See "8.3.7Schedule screen: Example"[4114].
Setpoint mode
Define the setpoint mode:
▪ Fixed: the desired leaving water temperature does not depend on the outdoor
ambient temperature.
▪ In WD heating, fixed cooling mode, the desired leaving water
temperature:
- depends on the outdoor ambient temperature for heating
- does NOT depend on the outdoor ambient temperature for cooling
▪ In Weather dependent mode, the desired leaving water temperature depends
on the outdoor ambient temperature.
# Code Description
[2.4] N/A Setpoint mode:
▪ Fixed
▪ WD heating, fixed cooling
▪ Weather dependent
When weather dependent operation is active, low outdoor temperatures will result
in warmer water and vice versa. During weather dependent operation, the user
can shift the water temperature up or down by a maximum of 10°C.
Heating WD curve
Set weather-dependent heating for the main zone (if [2.4]=1 or 2):