8 | Configuration
Installer reference guide
140
ERGA04~08DAV3(A) + EHBH/X04+08DA*V7
Daikin Altherma 3 R W
4P618958-1 – 2020.03
Setpoint range
For more information about Setpoint range, see "8.5.3Main zone"[4127].
# Code Description
Leaving water temperature range for the additional leaving water temperature
zone (= the leaving water temperature zone with the highest leaving water
temperature in heating operation and the lowest leaving water temperature in
cooling operation)
[3.8.1] [9-05] Heating minimum: 15°C~37°C
[3.8.2] [9-06] Heating maximum
[2‑0D]=2 (emitter type additional zone =
radiator)
37°C~60°C
Else: 37°C~55°C
[3.8.3] [9-07] Cooling minimum: 5°C~18°C
[3.8.4] [9-08] Cooling maximum: 8°C~22°C
# Code Description
Leaving water temperature range for the main leaving water temperature zone (=
the leaving water temperature zone with the lowest leaving water temperature in
heating operation and the highest leaving water temperature in cooling
operation)
[2.8.1] [9-01] Heating minimum:
15°C~37°C
[2.8.2] [9-00] Heating maximum:
[2‑0C]=2 (emitter type main zone = radiator)
37°C~70°C
Otherwise: 37°C~55°C
[2.8.3] [9-02] Cooling minimum:
5°C~18°C
[2.8.4] [9-03] Cooling maximum:
18°C~22°C
Control
The control type for the additional zone is read only. It is determined by the control
type of the main zone.
See "8.5.3Main zone"[4127].
# Code Description
[3.9] N/A Control:
Leaving water if the control type of the
main zone is Leaving water.
External room thermostat if the control
type of the main zone is:
- External room thermostat,or
- Room thermostat.