8 | Configuration
Installer reference guide
142
ERGA04~08DAV3(A) + EHBH/X04+08DA*V7
Daikin Altherma 3 R W
4P618958-1 – 2020.03
When the unit is in cooling mode, the icon is shown.
The status indicator shows if the unit is currently in operation:
When the unit is not in operation, the status indicator will show a blue pulsation
with an interval of approximately 5 seconds.
While the unit is in operation, the status indicator will light up blue constantly.
To set the space operation mode
1 Go to [4.1]: Space heating/cooling > Operation mode
2 Select one of the following options:
Heating: Only heating mode
Cooling: Only cooling mode
Automatic: The operation mode changes automatically
based on the outdoor temperature. Restricted according to
the operation mode schedule.
Automatic heating/cooling changeover is only applicable for EHBX and EHVX.
When Automatic is selected, the unit switches its operation mode, based on the
Operation mode schedule [4.2]. In this schedule, the end user indicates which
operation is allowed for each month.
To restrict automatic changeover according to a schedule
Conditions: You set the space operation mode to Automatic.
1 Go to [4.2]: Space heating/cooling > Operation mode
schedule.
2 Select a month.
3 For each month, select an option:
Reversible: Not restricted
Heating only: Restricted
Cooling only: Restricted
4 Confirm the changes.
Example: Changeover restrictions
When Restriction
During cold season.
Example: October, November, December, January,
February and March.
Heating only
During warm season.
Example: June, July and August.
Cooling only
In-between.
Example: April, May and September.
Reversible
The unit determines its operation mode by the outdoor temperature if:
Operation mode=Automatic, and
Operation mode schedule=Reversible.
The unit determines its operation mode in such a way that it will always stay within
the following operation ranges: