Daikin Altherma 3 R W
4P618958-1 – 2020.03
Configuration
Via the user interface (configuration wizard):
▪ Set the use of a bivalent system as external heat source.
▪ Set the bivalent temperature and hysteresis.
NOTICE
▪ Make sure the bivalent hysteresis has enough differential to prevent frequent
changeover between indoor unit and auxiliary boiler.
▪ Because the outdoor temperature is measured by the outdoor unit air
thermistor, install the outdoor unit in the shadow so that it is NOT influenced or
turned ON/OFF by direct sunlight.
▪ Frequent changeover may cause corrosion of the auxiliary boiler. Contact the
manufacturer of the auxiliary boiler for more information.
Changeover to external heat source decided by an auxiliary contact
▪ Only possible in external room thermostat control AND one leaving water
temperature zone (see "5.2Setting up the space heating/cooling system"[423]).
▪ The auxiliary contact can be:
- An outdoor temperature thermostat
- An electricity tariff contact
- A manually operated contact
- …
▪ Setup: Connect the following field wiring:
B
TI
Boiler thermostat input
A Auxiliary contact (normally closed)
H Heating demand room thermostat (optional)
K1A Auxiliary relay for activation of indoor unit (field supply)
K2A Auxiliary relay for activation of boiler (field supply)
Indoor Indoor unit
Auto Automatic
Boiler Boiler
NOTICE
▪ Make sure the auxiliary contact has enough differential or time delay to prevent
frequent changeover between indoor unit and auxiliary boiler.
▪ If the auxiliary contact is an outdoor temperature thermostat, install the
thermostat in the shadow so that it is NOT influenced or turned ON/OFF by direct
sunlight.
▪ Frequent changeover may cause corrosion of the auxiliary boiler. Contact the
manufacturer of the auxiliary boiler for more information.