Component V3 W1
ERHQ ERLQ ERHQ ERLQ
Earth leakage circuit breaker Must comply with applicable
legislation
(a) MCA=Minimum circuit ampacity. Stated values are
maximum values (see electrical data of combination with
indoor units for exact values).
7.9.6 To connect the electrical wiring on the
outdoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1 Remove the service cover. See "7.2.2 To open the outdoor
unit"on page29.
2 Strip insulation (20mm) from the wires.
a Strip wire end to this point
b Excessive strip length may cause electrical shock or
leakage.
3 Connect the interconnection cable and power supply as follows:
c
b
a
d
V3
1~ 50 Hz
230 V
W1
3N~ 50 Hz
400 V
L1 L3L2
L1 L3L2
a Interconnection cable
b Power supply cable
c Earth leakage circuit breaker
d Fuse
a Switch box
b Stop valve attachment plate
c Earth
d Cable tie
e Interconnection cable
f Power supply cable
Only if bottom plate heater is installed (option for ERHQ):
g Bottom plate heater cable
h Power supply cable of the bottom plate heater (from the
indoor unit)
INFORMATION
ERLQ units control the bottom plate heater internally (field
wiring NOT required).
4 Fix the cables (power supply, interconnection cable and power
supply of the bottom plate heater (if applicable)) with a cable tie
to the stop valve attachment plate.
5 Route the wiring through the frame and connect it to it.
Routing through
the frame
Choose one of the 3 possibilities:
a Power supply, earth wiring, and bottom
plate heater wire (if applicable)
b Interconnection cable