14 Technical data
Installer reference guide
117
ERHQ+ERLQ011~016 + EHBH/X11+16CB
Daikin Altherma – Low temperature split
4P384974-1 – 2015.01
Heating only type Reversible type
Indoor units EHBH11+16/EHVH11+16 EHBX11+16/EHVX11+16
Outdoor units ERHQ011BAW1 ERHQ014BAW1 ERHQ016BAW1 ERHQ011BAW1 ERHQ014BAW1 ERHQ016BAW1
Drain Quantity 4
Type Hole
Diameter (OD) 3ר26+1ר18mm
Piping length Minimum 3m
Maximum 75m
Equivalent 95m
Chargeless 10m
Additional refrigerant charge See "To determine the additional refrigerant amount"
Maximum height difference
between outdoor unit and indoor
unit
30m
Equivalent height difference —
Maximum interunit level
difference
—
Heat insulation Both liquid and gas pipe
Defrost method Pressure equalising
Defrost control Sensor for outdoor heat exchanger temperature
Capacity control method Inverter controlled
Capacity control (%) —
Safety devices High pressure switch / Fan motor thermal protector / Fuse
Standard accessories 1 installation manual / 2 tie wraps
(a) See operation range drawing.
(b) Range increase by support backup heater.
(c) Range increase by support booster heater.
(d) Ambient temperature DB/WB 7°C/6°C – leaving water condenser 35°C (ΔT=5°C).
(e) Ambient temperature 35°C – leaving water evaporator 7°C (ΔT=5°C)
(f) The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and
acoustic environment. Refer to the sound spectrum drawing for more information.
Electrical specifications: ERHQ_W1
Heating only type Reversible type
Indoor units EHBH11+16/EHVH11+16 EHBX11+16/EHVX11+16
Outdoor units ERHQ011BAW1 ERHQ014BAW1 ERHQ016BAW1 ERHQ011BAW1 ERHQ014BAW1 ERHQ016BAW1
Power supply
Name W1
Phase 3N~
Frequency 50Hz
Voltage 400V
Voltage range Minimum 360V
Maximum 440V
Current
Nominal
running current
Cooling —
Heating
(a)
5.8A
Starting current —
Maximum running current
(cooling and heating)
13.5A
Z
max
—
Minimum S
sc
value —
Recommended fuses 20A
Wiring connections
For power supply See "Connecting electrical wiring"
For connection with indoor
Power supply intake Outdoor unit only
(a) Ambient temperature DB/WB 7°C/6°C – leaving water condenser 35°C (ΔT=5°C).