[Commonly used eld setting items]
ModeNo.
Note1)
FIRST
CODENo.
Description of setting
SECONDCODENo.
01 02 03
10(20)
0
Note3)
FilterContamination-Heavy/Light
(Setting for spacing time of display
timetocleanairlter)
(Settingforwhenltercontamination
isheavy,andspacingtimeofdisplay
timetocleanairlteristobehalved)
Ultra-long-
life type
Light
Approx.
10,000Hrs
Heavy
Approx.
5,000Hrs
–
Longlife
Filter
Approx.
2,500Hrs
Approx.
1,250Hrs
Standard
Filter
Approx.
200 Hrs
Approx.
100 Hrs
1
Note3)
Long-lifeltertype
(Settingofltersignindicationtime)
(ChangesettingwhenUltra-long-lifelteris
installed)
Long-life
lter
Ultra-long-
lifelter
–
2 Thermostat sensor in remote controller Use Notuse –
11(21) 0
SettingnumberofconnectedSkyairsimultaneous
operation System indoor unit
(Setting for Simultaneous operation system)
Pair Twin –
12(22) 1 ON/OFFinputfromoutside ForcedOFF
ON/OFF
operation
–
13(23)
0
HighCeilingSetting(Settingforwheninstalledin
a Ceiling higher than 2.7m)
* Height depends on the connected model.
Refer to the installation manual attached to the
indoor unit to be connected for details.
≤2.7m*
2.7m<,
≤3.0m*
3.0m<,
≤3.5m*
1
SelectionofAirowDirection
(Settingforwhenablockingpadkithasbeen
installed)
4-wayow 3-wayow 2-wayow
3
AirowDirectionAdjustmentFunction
(Tobesetwhendecorationpanelforairoutlet
installed)
Equipped
No
Equipped
–
4 AirowDirectionRangeSetting Upper Normal Lower
6
SettingtheExternalStaticpressure
(Setting according to the connected duct
resistance)
(ForFHYK,followthehighCeilingSetting)
Normal
High static
pressure
Lowstatic
pressure
15(25)
1 HumidifyingwiththermostatOFF
No
Equipped
Equipped –
3 Drainpumpoperationwithhumidifying
No
Equipped
Equipped –
Note:
1)Incasethereisaneedtoperformanysettingnotlistedinthetableabove,pleaserefertothe
installation manual of each indoor unit.
2)Somefunctionswillbenotdisplayediftheindoorunitisnotequippedwiththatfunction.
3)Thismodeisusedtosetthetimeuntilthedisplaytimetocleanairlterlightsupwhenusinga
central remote controller.