2 | Troubleshooting
Service manual
17
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
6 Check if the refrigerant circuit is correctly charged. See "4.2 Refrigerant
circuit"[4286].
Possible cause: Refrigerant overcharge.
7 Check if the refrigerant circuit is clogged. See "4.2Refrigerant circuit"[4286].
Possible cause: Clogged refrigerant circuit.
8 Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See "4.2Refrigerant circuit"[4286].
Possible cause: Non‑condensables and/or humidity in the refrigerant circuit.
9 Check the water flow. See "4.3Water circuit"[4299].
Possible cause: Water flow is too low.
10 Check the water pressure. See "4.3Water circuit"[4299].
Possible cause: Water pressure is too low.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.9 89-02 – Heat exchanger frozen
Trigger Effect Reset
Condensing temperature
<0°C during space
heating.
Unit will stop operating. Automatic reset.
Liquid refrigerant
thermistor ≤0°C during
space heating or domestic
hot water.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the 4‑way valve. See "3.24-way valve"[496].
Possible cause: Faulty 4‑way valve.
2 Perform a check of the main PCB. See "3.14Main PCB"[4171].
Possible cause: Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.