2 | Troubleshooting
Service manual
31
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
5 Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See "4.2Refrigerant circuit"[4286].
Possible cause: Non‑condensables and/or humidity in the refrigerant circuit.
6 Check if the refrigerant circuit is clogged. See "4.2Refrigerant circuit"[4286].
Possible cause: Clogged refrigerant circuit.
7 Perform a check of the outdoor unit fan motor. See "3.16 Outdoor unit fan
motor"[4217].
Possible cause: Faulty outdoor unit fan motor.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.28 E4-00 – Abnormal suction pressure
Trigger Effect Reset
Suction pressure was too
low (detected by
thermistor/pressure
sensor or low pressure
switch) for several times.
Unit will stop operating. Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the suction pipe thermistor. See
"3.20Thermistors"[4248].
Possible cause: Faulty suction pipe thermistor or connector fault.
2 Check that all stop valves of the refrigerant circuit are open. See
"4.2Refrigerant circuit"[4286].
Possible cause: Closed stop valve in the refrigerant circuit.
3 Check if the refrigerant circuit is correctly charged. See "4.2 Refrigerant
circuit"[4286].
Possible cause: Refrigerant shortage.
4 Check for the presence of humidity in the refrigerant circuit. See
"4.2Refrigerant circuit"[4286].
Possible cause: Humidity in the refrigerant circuit.
5 Check if the refrigerant circuit is clogged. See "4.2Refrigerant circuit"[4286].
Possible cause: Clogged refrigerant circuit.
6 Perform a check of all expansion valves. See "3.9Expansion valve"[4149].
Possible cause: Faulty expansion valve.
7 Check the required space around the outdoor unit heat exchanger. See
"4.5External factors"[4307].
Possible cause: Insufficient air flow or air by‑pass due to required space
specifications not met.

Table of Contents

Other manuals for Daikin EBLA16DA3V3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin EBLA16DA3V3 and is the answer not in the manual?

Daikin EBLA16DA3V3 Specifications

General IconGeneral
BrandDaikin
ModelEBLA16DA3V3
CategoryHeat Pump
LanguageEnglish

Related product manuals