2 | Troubleshooting
Service manual
30
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
5 Check if the refrigerant circuit is correctly charged. See "4.2 Refrigerant
circuit"[4286].
Possible cause: Refrigerant overcharge.
6 Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See "4.2Refrigerant circuit"[4286].
Possible cause: Non‑condensables and/or humidity in the refrigerant circuit.
7 Check if the refrigerant circuit is clogged. See "4.2Refrigerant circuit"[4286].
Possible cause: Clogged refrigerant circuit.
8 Perform a check of the outdoor unit fan motor. See "3.16 Outdoor unit fan
motor"[4217].
Possible cause: Faulty outdoor unit fan motor.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.27 E3-24 – High pressure switch abnormality
Trigger Effect Reset
High pressure switch
opens due to measured
pressure above high
pressure switch operating
point.
Unit will stop operating. Manual reset via user
interface.
High pressure control
(measured pressure just
below high pressure
switch operating point)
occurs 16 times within
300minutes.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the refrigerant pressure sensor. See "3.19 Refrigerant
pressure sensor"[4244].
Possible cause: Faulty refrigerant pressure sensor.
2 Perform a check of the high pressure switch. See "3.11 High pressure
switch"[4157].
Possible cause: Faulty high pressure switch.
3 Perform a check of the main PCB. See "3.14Main PCB"[4171].
Possible cause: Faulty main PCB.
4 Check if the refrigerant circuit is correctly charged. See "4.2 Refrigerant
circuit"[4286].
Possible cause: Refrigerant overcharge.

Table of Contents

Other manuals for Daikin EBLA16DA3V3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin EBLA16DA3V3 and is the answer not in the manual?

Daikin EBLA16DA3V3 Specifications

General IconGeneral
BrandDaikin
ModelEBLA16DA3V3
CategoryHeat Pump
LanguageEnglish

Related product manuals