2 | Troubleshooting
Service manual
28
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
▪ Measure the room temperature and compare to the room temperature
shown on the user interface (remote controller).
▪ If temperature shown on the user interface differs from the measured
temperature, replace the user interface (remote controller). See
documentation of the user interface (remote controller) for more
information.
Possible cause: Faulty room thermistor.
2 Check the communication wiring between the remote controller and the unit.
See "3.21User interface"[4266].
Possible cause: Faulty wiring between the remote controller and the unit.
3 Perform a check of the hydro PCB. See "3.12Hydro PCB"[4160].
Possible cause: Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.25 E1-00 – Outdoor unit: PCB defect
Trigger Effect Reset
Main PCB detects that
EEPROM is abnormal.
Unit will stop operating. Manual reset via user
interface.
Power reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the main PCB. See "3.14Main PCB"[4171].
Possible cause: Faulty main PCB.
2 Check if the power supply is conform with the regulations. See "4.1Electrical
circuit"[4284].
Possible cause:
▪ Faulty or disturbance of the power supply (imbalance >4%),
▪ Power drop,
▪ Short circuit.
3 Perform a check of the outdoor unit fan motor. See "3.16 Outdoor unit fan
motor"[4217].
Possible cause: Faulty outdoor unit fan motor.
4 Perform a check of the compressor. See "3.7Compressor"[4134].
Possible cause: Faulty compressor or miswiring of the compressor power
supply cable.
Prerequisite: Stop the unit operation via the user interface.
5 Turn OFF the respective circuit breaker.