Troubleshooting by Remote Controller ESIE09-05
154 Troubleshooting
2. Troubleshooting by Remote Controller
2.1 The INSPECTION / TEST Button
The following modes can be selected by using the [Inspection/Test Operation] button on the
remote control.
Normal
mode
Inspection
mode
Test
operation
mode
Local
setting
mode
Service
mode
Press Inspection/Test Operation button
for more than 4 seconds.
Press Inspection/Test Operation button
for more than 4 seconds.
Press Inspection/Test Operation button once.
Press Inspection/Test Operation button once.
Or after 30 minutes
After 10 seconds
Press Inspection/Test Operation
button once.
Press Inspection/Test Operation
button once.
AHU settings can be made
• Others
Following codes can be checked.
• Malfunction codes
Service data can be obtained.
• Malfunciton code history
• Temperature data of various sections
Service settings can be made.
• Forced fan ON
• Air ow direction/volume setting
Thermostat is forcibly turned on.
(V0815)