ESIE09-05 Special Control
Function 31
3.5 Restart Standby
Restart is stood by force to prevent frequent power-on/off and to equalize pressure in the
refrigerant system.
Actuator Operation
Compressor OFF
Outdoor unit fan
Ta>30°C: STEP4
Ta≤30° C: OFF
Four way valve Keep former condition.
Main electronic expansion valve (EV1) 0 pls
Subcooling electronic expansion valve (EV3) 0 pls
Hot gas bypass valve (SVP) OFF
Ending conditions 2 min.