EasyManua.ls Logo

Daikin EWAQ032BAW - EW*Q021 BA, 025 BA, 040 BA Module, 050 BA Module

Daikin EWAQ032BAW
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ESIE11-05 List of Electrical and Functional Parts
Service Procedure 183
1.2 EW*Q021BA, 025BA, 040BA Module, 050BA Module
Item Name Symbol
Compressor
Inverter
Type
M1C
JT1GCVDKYR@T
OC protection
device
14.7A
STD 1
Type
M2C
JT170G-KYE@T
OC protection
device
15.0A
STD 2
Type
M3C
OC protection
device
Fan motor
OC protection
device
M1F 3A 1.15A
Electronic expansion valve coil (Main) Y1E Fully closed: 0pls Fully open: 480pls
Electronic expansion valve coil (Subcool) Y2E Fully closed: 0pls Fully open: 480pls
Pressure
protection
High pressure
switch
For M1C S1PH OFF: 4.0 MPa ON: 3.0±0.15MPa
For M2C S2PH OFF: 4.0 MPa ON: 3.0±0.15MPa
For M3C S3PH
Low pressure sensor S1NPL OFF: 0.07MPa
Temperature
protection
Discharge gas temperature
protection
(Discharge pipe thermistor)
R3T OFF: 135°C
Inverter fin temperature
protection
(Radiator fin thermistor)
R1T OFF: 93°C
Others Fuse
For main PCB
A1P 250V, 15A
A2P 250V, 3A
For Noise filter
PCB
F1U 250V AC 5A Class B
0
0.12
0
0.12

Table of Contents