Field Setting from Outdoor Unit ESIE11-05
68 Functional Description
Dipswitch
settings for the
applicable
models
Setting by BS
button switches
The following settings are made by BS button switches on PCB.
In case of EW*Q040BA, 050BA, 064BA, various items should be set with the master unit.
(Setting with the slave unit is disabled.)
The master unit and slave unit can be discriminated with the LED display as shown below.
(Factory setting)
There are the following three setting modes.
Setting mode 1 (H1P off)
Initial status (when normal): Used to select IND/BATCH. Also indicates during “abnormal”, “low
noise control” and “demand control”.
Setting mode 2 (H1P on)
Applicable model
Settings
Positions Switches ON
EWYQ016BAWP (H/P)
EWYQ016BAWN (H/P)
DS1-4, DS2-3
EWYQ021BAWP (H/P)
EWYQ021BAWN (H/P)
EWYQ040BAWP (H/P)
EWYQ040BAWN (H/P)
DS1-4, DS2-2, DS2-3
EWYQ025BAWP (H/P)
EWYQ025BAWN (H/P)
EWYQ050BAWP (H/P)
EWYQ050BAWN (H/P)
DS1-4, DS2-4
EWYQ032BAWP (H/P)
EWYQ032BAWN (H/P)
EWYQ064BAWP (H/P)
EWYQ064BAWN (H/P)
DS1-4, DS2-3, DS2-4
EWAQ016BAWP (C/O)
EWAQ016BAWN (C/O)
DS1-3, DS1-4, DS2-3
EWAQ021BAWP (C/O)
EWAQ021BAWN (C/O)
EWAQ040BAWP (C/O)
EWAQ040BAWN (C/O)
DS1-3, DS1-4, DS2-2, DS2-3
EWAQ025BAWP (C/O)
EWAQ025BAWN (C/O)
EWAQ050BAWP (C/O)
EWAQ050BAWN (C/O)
DS1-3, DS1-4, DS2-4
EWAQ032BAWP (C/O)
EWAQ032BAWN (C/O)
EWAQ064BAWP (C/O)
EWAQ064BAWN (C/O)
DS1-3, DS1-4, DS2-3, DS2-4
LED display
MODE
H1P
TEST
H2P
COOL/HEAT select Low
noise
H6P
Demand
H7P
Multi
H8P
IND
H3P
MASTER
H4P
SLAVE
H5P
Single-outdoor-unit
system
hhkhhhhh
EW*Q040BA,
050BA,
064BA
Master
hhkhhhhk
Slave 1
hh h h h h h l
BS1
MODE
BS2
SET
BS3
RETURN
BS4
TEST
BS5
RESET