ESIE11-05 Other Control
Functional Description 61
5.2 Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using “Demand 1 Setting” or “Demand 2 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting” or
external input by external control adaptor is required.
See page 193 for more information.
Set item Condition Content
Demand 1 Mode 1 The compressor operates at approx. 60% or less of rating.
Mode 2 The compressor operates at approx. 70% or less of rating.
Mode 3 The compressor operates at approx. 80% or less of rating.
Demand 2 The compressor operates at approx. 40% or less of rating.
Demand 3 Forced thermostat OFF.