ESIE11-05 Options
Service Procedure 191
5.1.2 Field Settings
[6-01] External room thermostat option:
Setting [6-01]=1
Room thermostat input 1= heating thermo ON(1)/OFF(0)
Room thermostat input 2= cooling thermo ON(1)/OFF(0)
Setting [6-01]=2
Room thermostat input 1= thermo ON(1)/OFF(0)
Room thermostat input 2= cooling(1)/heating(0)
5.1.3 Explanation
Thermostat ON/
OFF
The unit still cycles water but can not start to cool/heat.
Example:
The unit is running and a thermo OFF command is given. The unit stops with a pump down. It
will not restart the compressors until a thermo ON command is given and there is load.
Also the output signal of the unit shows the unit active.
Cooling/heating The unit will switch between cooling and heating and vice versa.
Operation ON/
OFF
The unit will stop completely and the output ON/OFF is 0.