Outline of Control (Hydrobox) ESIE11-05
64 Functional Description
6.3 Flow Control
6.3.1 Unit State OPERATION LED ON
Pump starts.
If no flow detected for 2 min unit stops and gives A6 error.
6.3.2 Unit State RUN COOLING/HEATING
Pump ON.
If no flow, unit will decrease capacity to keep the unit in safe situation sensor R13T and
R14T.
No flow, for 40 sec unit thermo off.
No flow for 2 min pump off, unit gives A6 error.
6.3.3 Unit State DEFROST
Pump ON.
If no flow, unit will decrease capacity to keep the unit in safe situation sensor R13T and
R14T.
No flow for 30 sec: unit thermo off.
No flow for 2 min pump off, unit gives A6 error.