Special Control ESIE11-05
52 Functional Description
3.5 Stopping Operation
3.5.1 When System is in Stop Mode (Normal Operation Stop)
This mode is used to define actuator operations when the system stops.
* Actuators are based on EWYQ032BA.
Actuator Operation
Compressor OFF
Outdoor unit fan OFF
Four way valve Holds
Main electronic expansion valve (EV1) 0 pls
Subcooling electronic expansion valve (EV2) 0 pls
Hot gas bypass valve (SVP) OFF
Accumulator oil return valve (SVO) OFF
Hydrobox electronic expansion valve (K11E) 0 pls
Hydrobox electronic expansion valve (K21E) 0 pls
Ending conditions Hydrobox thermostat is turned ON.