Other Control ESIE11-05
60 Functional Description
5.1.3 In the Case of EW*Q040BA-064BA Module
Emergency
operation with
settings in
service mode
“Inhibition of operation” is set with each outdoor unit module.
Make the following settings with the master unit. (Setting with the slave unit becomes disabled.)
Discriminate the operating status of the master unit / slave units through the following LED
display.
In order to set the master unit to operation
prohibition mode, set No. 38 of Setting mode 2
to "MASTER OPERATION PROHIBITION".
(Procedure)
(1) Press and hold the MODE button (BS1) for a
period of 5 seconds or more.
(2) Press the SET button (BS2) 38 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
In order to set the slave unit 1 to operation
prohibition mode, set No. 39 of Setting mode 2
to "SLAVE 1 OPERATION PROHIBITION".
(Procedure)
(1) Press and hold the MODE button (BS1) for a
period of 5 seconds or more.
(2) Press the SET button (BS2) 39 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
In order to set the slave unit 2 to operation
prohibition mode, set No. 40 of Setting mode 2
to "SLAVE 2 OPERATION PROHIBITION".
(Procedure)
(1) Press and hold the MODE button (BS1) for a
period of 5 seconds or more.
(2) Press the SET button (BS2) 40 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
In the case of EW*Q040BA-064BA module, “Inhibition of operation” is not set with each
compressor individually.
In the case of EW*Q040BA-064BA module, when the above “Inhibition of operation” is set,
outdoor unit rotation is not functional.