Field Setting from Outdoor Unit ESIE11-05
80 Functional Description
: ON : OFF l: Blink

Setting
No.
Setting
contents
Setting No. indication Setting No. indication Setting
contents
Setting contents indication (Initial setting)
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
12 External
low noise /
Demand
setting

NO
(Factory
setting)
 l
YES
 l
22 Night-time
low noise
setting
OFF
(Factory
setting)

Mode 1
 l
Mode 2
 l
Mode 3
 l l
25 External
low noise
setting
Mode 1
 l
Mode 2
(Factory
setting)
 l
Mode 3
 l
26 Night-time
low noise
operation
start setting
PM 8:00
 l
PM 10:00
(Factory
setting)
 l
PM 0:00
 l
27 Night-time
low noise
operation
end setting
AM 6:00
 l
AM 7:00
 l
AM 8:00
(Factory
setting)
 l
29 Capacity
priority
setting
Low noise
priority
(Factory
setting)
 l
Capacity
priority
 l
30 Demand
setting 1
60% of
rated power
consumption
 l
70% of
rated power
consumption
(Factory
setting)
 l
80% of
rated power
consumption
 l
32 Normal
demand
setting
OFF
(Factory
setting)
 l
ON
 l
Setting mode indication section Setting No. indication section Set contents indication section