Remote Controller ESIE11-05
86 Functional Description
Field settings
table
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value
0 Remote control setup
00 User permission level 22~31
01 Room temperature compensation value 0 –5~5 0.5 °C
02 Not applicable. Do not change the default value. 1
03 Status: space heating schedule timer mode
Method 1=1 / Method 2=0
1 (ON) 0/1
04 Status: space cooling schedule timer mode
Method 1=1 / Method 2=0
1 (ON) 0/1
1 Settings are not applicable
00 Not applicable. Do not change the default value. 1
01 Not applicable. Do not change the default value. 1:00
02 Not applicable. Do not change the default value. 0
03 Not applicable. Do not change the default value. 15:00
2 Automatic setback function
00 Status: setback operation 1 (ON) 0/1
01 Setback operation start time 23:00 0:00~23:00 1:00 hour
02 Setback operation stop time 5:00 0:00~23:00 1:00 hour
3 Weather dependent set point
00 Low ambient temperature (Lo_A) –10 –20~5 1 °C
01 High ambient temperature (Hi_A) 15 10~20 1 °C
02 Set point at low ambient temperature (Lo_Ti) 40 25~80 1 °C
03 Set point at high ambient temperature (Hi_Ti) 25 25~80 1 °C
4 Settings are not applicable
00 Not applicable. Do not change the default value. 1
01 Not applicable. Do not change the default value. Fri
02 Not applicable. Do not change the default value. 23:00
5 Automatic setback
00 Not applicable. Do not change the default value. 70
01 Not applicable. Do not change the default value. 10
02 Leaving water setback temperature 5 0~10 1 °C
03 Room setback temperature 18 17~23 1 °C
04 Not applicable. Do not change the default value. 1
6 Option setup
01 Optional room thermostat installed 0 0~2
03 Negative leaving water temperature setting 0 0~–10 –1 °C
7 Option setup
00 Forced pump operation 1 (ON) 0/1
8 Option setup
00 Remote controller temperature control 0 (OFF) 0/1
01 Not applicable. Do not change the default value. 1
03 Not applicable. Do not change the default value. 1
04 Status: freeze-up prevention 0 0~2 1