SiUS091601EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 162
Reference
Reference
Reference
Troubleshooting
Check No.01 Refer to P.181
Check No.13 Refer to P.185
Check No.14 Refer to P.185
NG
OK
NO
OK
NG
OK
YES
NG
Correct the four way valve
coil.
Reconnect the harness.
YES
YES
YES
NO
NO
Replace the outdoor
unit PCB (main PCB).
Replace the defective
thermistor(s).
Refer to the refrigerant line
check procedure.
Replace the four way valve
(defective or dust-clogged).
Reconnect the
thermistor(s).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
(R20405)
Refrigerant shortage
Water mixed
Stop valve
Four way valve
coil disconnected (loose)?
Harness
disconnected?
Any thermistor
disconnected?
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant line.
Check No. 13
Check the four way valve
switching output.
Check the continuity of the four way
valve coil and harness.
Replace the four way
valve coil.
NO
Resistance
between harnesses
about 1000 ~ 2000 Ω?
Disconnect the harness from the
connector.

Table of Contents

Other manuals for Daikin FDMQ-R Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FDMQ-R Series and is the answer not in the manual?

Daikin FDMQ-R Series Specifications

General IconGeneral
BrandDaikin
ModelFDMQ-R Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals