EasyManua.ls Logo

Daikin FTXS09HVJU - Page 108

Daikin FTXS09HVJU
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service Check Function SiUS04-904
Service Diagnosis 97
5. Press the TEMP button.
Press TEMP
or buttonand change the figure until you hear the long beep.
6. Diagnose by the sound.
beep: The left-side numeral is incorrect; move to the next number.
beep-beep: The right-side number is incorrect; move to the next number.
long beeeeep: Both numbers are correct; this is your error code. Refer to the troubleshooting
section to learn more about his code.
7. Determine the error code.
The figure indicated when you hear the long beep sound is the error code.
(Error codes and description
Refer to page 98.)
8. Press the MODE button to exit from the diagnosis mode.
The display “ ” means the trial operation mode.
(Refer to page 262 for trial operation.)
9. Press the ON/OFF button twice to return to the normal mode.
Note: When the remote controller is left untouched for 60 seconds, it returns to the normal mode.
(R8383)
(R8384)
(R9879)
(R9660)

Table of Contents