Main Functions SiUS04-904
28 Function and Control
Ex: When the set point is 77°F (25°C)
Cooling Operation 73.4°F(23°C): Thermostat OFF 72°F(22°C): Switch to Heating
Operation
Heating Operation 79.7°F(26.5°C): Thermostat OFF 81.5°F(27.5°C): Switch to
Cooling Operation
1.6 Thermostat Control
Thermostat control is based on the difference between the room temperature and the setpoint.
Thermostat OFF Condition
The temperature difference is in zone A.
Thermostat ON Condition
The temperature difference is above zone C after being in zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in zone B.
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
Cooling / Dry
Heating Operation
Cooling Operation
Set point – Δ3.6ºF(2.0ºC)
Set point – Δ4.5ºF(2.5ºC)
Set point + Δ4.5ºF(2.5ºC)
Set point + Δ2.7ºF(1.5ºC)
B
A
OFF
OFF
ONON
C
Cooling : –Δ0.9°F (0.5°C)
Dry : –Δ0.9°F (0.5°C)
Room temperature – set point
Cooling : –Δ3.6°F (2°C)
Dry : –Δ4.5°F (2.5°C)~–Δ3.6°F (2.0