SiUS04-904 Control Specification (09/12 Class)
Function and Control 37
Detail How to Determine Frequency
The compressor’s frequency is determined by taking the following steps:
1. Determine command frequency
Command frequency is determined in the following order of priority.
1.1 Limiting defrost control time
1.2 Forced cooling
1.3 Indoor frequency command
2. Determine upper limit frequency
Set a minimum value as an upper limit frequency among the frequency upper limits of the
following functions:
Compressor protection, input current, discharge pipe temperature, heating peak-cut, freeze-up
protection, defrost.
3. Determine lower limit frequency
Set a maximum value as an lower limit frequency among the frequency lower limits of the
following functions:
Four-way valve operation compensation, draft prevention, pressure difference stabilization .
4. Determine prohibited frequency
There is a certain prohibited frequency such as a power supply frequency.