EasyManua.ls Logo

Daikin FTXS09HVJU - Defrost Control

Daikin FTXS09HVJU
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control Specification (15/18/24 Class) SiUS04-904
56 Function and Control
4.11 Defrost Control
Outline Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat
exchanger temperature must be more than its fixed value when finishing.
Detail Conditions for Starting Defrost
The starting conditions must be made with the outdoor air temperature and heat exchanger
temperature. Under the conditions that the system is in heating operation, 6 minutes after the
compressor is started and more than 44 minutes of accumulated time pass since the start of the
operation or ending the defrosting.
Conditions for Canceling Defrost
The judgment must be made with heat exchanger temperature. (39°F~54°F / 3.8~12.2°C)
Frequency
Compressor
Four way valve
Fan
Electronic expansion
valve opening
ON
OFF
ON
OFF
ON
OFF
0Hz
5sec.
450pulse450pulse450pulse
Initial opening
PI control
5sec.
45sec.60sec. 460 sec.
120sec.
(R4082)

Table of Contents

Other manuals for Daikin FTXS09HVJU

Related product manuals