Main Functions SiUS04-904
32 Function and Control
operation or when the powerful operation button is pressed.
Others The set temperature and set air volume are memorized in the remote controller. When the remote
controller is reset due to replacement of battery, it is necessary to set the temperature and air
volume again for [HOME LEAVE].
1.10 Inverter POWERFUL Operation
Outline To enhance the cooling and heating capacity, operate the air conditioner by increasing the indoor
fan rotating speed and the compressor frequency.
Details of the
Control
When the POWERFUL button is pushed in each operation mode, the fan speed and setting
temperature are converted to the following states in a period of 20 minutes.
Operation mode Fan speed Target set temperature
COOL H tap + 90 rpm 64°F (18°C)
DRY Dry rotating speed +
50 rpm
Normally targeted
temperature in dry
operation; Approx. –3.6°F
(2.0°C)
HEAT H tap + 90 rpm 86°F (30°C)
FAN H tap + 90 rpm
AUTO Same as cooling /
heating in POWERFUL
operation
The target is kept
unchanged