Control Specification (09/12 Class) SiUS04-904
46 Function and Control
3.11.7 Control when frequency is changed
When the target discharge pipe temperature control is active, if the target frequency is changed for
a specified value in a certain time period, cancel the target discharge pipe temperature control and
change the target opening of the electronic expansion valve according to the shift.
3.11.8 Target Discharge Pipe Temperature Control
Obtain the target discharge pipe temperature from the indoor and outdoor heat exchanger
temperature, and adjust the electronic expansion valve opening so that the actual discharge pipe
temperature becomes close to that temperature. (Indirect SH(superheating) control using the
discharge pipe temperature)
The electronic expansion valve opening and the target discharge pipe temperature are adjusted
every 20 seconds. The target discharge pipe temperature is controlled by indoor heat exchanger
temperature and outdoor heat exchanger temperature. The opening degree of the electronic
expansion valve is controlled by following:
®The target discharge pipe temperature
®The actual discharge pipe temperature
®The previous discharge pipe temperature
Supercool)
(Superheat)
(R10626)