EasyManua.ls Logo

Daikin MPS - EBTRON or Field OA Flow Station Wiring

Daikin MPS
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EBTRON or Field OA Flow Station Wiring
MPS (17-50 Tons)/DPS Expansion Module B
X 2 X Reheat #1 0–10 VDC 1 = 2 & 28 = 2
X 3 X Gas Heat LS2 Switch Dry Contact 1 = 0 & 10 = 4
X 3 X OA Flow 0–10 VDC or 4–20 mA
1 = 2, 3 or 4 & 8 = 1, 2, 3, 5, 6 or 7 & 9 = 6
& 30 ≠ 3, 4, 5 or 6
X 4 X FSG Alarm Input (FSG-3) 1=0 & (10=3 or 10=4)
X 4 X Supply Temp Leaving Wheel 10K Thermistor (STD) 1 = 2, 3 or 4 & 20 > 0 & 30 ≠ 3, 4, 5 or 6
X 5 X Exhaust Temp Leaving Wheel 10K Thermistor (STD) 1 = 2, 3 or 4 & 20 > 0 & 30 ≠ 3, 4, 5 or 6
See Table 8 on page 18
RTU/SCU/MPS (62-70 Tons) Expansion Module E
# DI AI DO AO Point Comments Cong. Code Condition
X 1 X OA Flow 0–10 VDC or 4–20 mA 1 = 0 & 8 = 1, 2, 3, 5, 6 or 7 & 9 = 6
X 2
On Maverick (MPS) and Rebel (DPS) units the OA ow station
needs to be wired to terminals X3 and M on expansion module
B. On Rooftop (RTU) and Self Contained (SCU) units, the
OA ow station needs to be wired to terminals X1 and M on
expansion module E. Terminal M is common for all analog
inputs. Make sure the polarity is correct on the eld wiring to
read a valid CFM value. See Table 13 on page 23
IM 919-3 • MICROTECH III CONTROLLER 30 www.DaikinApplied.com
fIeld wIrIng

Other manuals for Daikin MPS

Related product manuals