unIT ConfIguraTIon seTup Menu
After the main control board application software is loaded
into the MCB, it must be “congured” for the specic
control application. This consists of setting the value of 28
conguration variables within the MCB. These variables dene
things such as the type of cooling, number of compressors and
cooling stages and the type of heat. If all of these items are not
set appropriately for the specic unit, the unit will not function
properly. The correct settings for these parameters are dened
for a given unit by the unit “Software Conguration Code.”
The “Software Conguration Code” consists of a 28-character
string of numbers and letters. The code can be found on the
Unit Software Identication Label located on the back side of
the control panel door. Table 29 lists the conguration code
variables including the position within the code, description
of the parameter, and the applicable settings for each. The
default values are shown in bold font. The unit is congured at
the factory, however it may also be congured in the eld by
accessing the Unit Conguration Menu. Once changes have
been made to the Unit Conguration Menu, the Apply Changes
ag must be changed from no to yes in order for the controller
to recognize the changes. Setting the Apply Changes ag to
YES will automatically reset the controller.
Table 23: Unit Conguration Menu
Conguration
Code Position
Description Values (Default in Bold) Special Condition RTU MPS DPS DPH SCU
1 Unit Type
0=Applied Rooftop (RTU)
1=Self-Contained (SCU)
2=Commercial Rooftop (MPS)
3=Rebel Cool Only (DPS)
4=Rebel Heat Pump (DPH)
● ● ● ● ●
2 Control Type
0=Zone Control
1=DAT Control
2=1ZoneVAV
● ● ● ● ●
3 Cooling Type
0 = None
1=Standard Compressorized Clg
2=Chilled Water
3=F&BP
4=Variable Comp Circuit 1
5=Variable Comp Circuit 2
6=NA
7=NA)
8=NA)
9=Digital Comp 1 Circuit
10=Digital Comp 2 Circuits
● ● ● ● ●
4
Compressorized Cooling
Conguration
0=None
1=Generic Condenser
2=2Cmp/2Circ/3Stg
3=3Cmp/2Circ/4Stg
4=2Cmp/2Circ/2or6StgorVar
(6 stg if 7=2,3,4or5)
5=3Cmp/3Circ/3Stg_NoWRV
6=3Cmp/3Circ/3Stg_WRV
7=4Cmp/2Circ/4StgorVar
8=4Cmp/4Circ/4Stg_NoWRV
9=4Cmp/4Circ/4Stg_WRV
A=6Cmp/2Circ/6StgorVar
B=6Cmp/6Circ/6Stg_NoWRV
C=6Cmp/6Circ/6Stg_WRV
D=3Cmp/2Circ/5StgorVar
E=4Cmp/2Circ/5or8Stg
(8 stg if 7=2,3,4or5)
F=8Cmp/4Circ/8Stg
G=8Cmp/8Circ/8Stg
H=6Cmp/3Circ/6Stg
I=Not Used
J=3 Cmp/3Circ/4Stg
K=Spare
L=1Var/1Circ
M=Var/1STD/1Circ
● ● ● ● ●
5
Generic Condenser Stages /
VFD Comp Cfg
1 – 8 Stages (default = 8
0=NA
1=Single
2=Tandom
3=Trio
●
●
(if
4=4,
5or
6)
●
(if
4=4,
5or
6)
unIT ConfIguraTIon seTup Menu
www.DaikinApplied.com 41 IM 919-3 • MICROTECH III CONTROLLER