SiBE05-722EE Check
Service Diagnosis 109
5.9 Installation Condition Check
Check No.17
5.10 Discharge Pressure Check
Check No.18
Installation condition check
OK
Check the allowable
dimensions of the air
suction and
discharge area.
Is the airflow blocked by
obstacles or winds
blowing in the opposite
direction?
(R19401)
NG
YES
YES
NO
Is the discharged air
short-circuited?
NO
NO
YES
Is the outdoor heat
exchanger very dirty?
Change the installation
location or direction.
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Check the outdoor
temperature.
(The outdoor
temperature should be
within the operation range.)
Change the installation location
or direction.
(R19385)
YES
YES
YES
NO
NO
NO
NO
YES
Is the air
filter or indoor / outdoor
heat exchanger
dirty?
Is the connection pipe
deformed?
Is the stop valve open?
High?
Replace the compressor.
Open the stop valve.
Replace the pipe installed at
the site.
Clean the dirty air filter or
indoor / outdoor heat
exchanger.
Replace the compressor.
Discharge pressure check

Table of Contents

Other manuals for Daikin RXS25K3V1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin RXS25K3V1B and is the answer not in the manual?

Daikin RXS25K3V1B Specifications

General IconGeneral
BrandDaikin
ModelRXS25K3V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals