SiBE05-722EE Control Specification
Functions and Control 45
3.3.3 Four Way Valve Operation Compensation
Outline At the beginning of operation as the four way valve is switched, the pressure difference to
activate the four way valve is acquired when the output frequency is higher than a certain fixed
frequency, for a certain fixed time.
Detail Starting Conditions
1. When the compressor starts and the four way valve switches from OFF to ON
2. When the four way valve switches from ON to OFF during operation
3. When the compressor starts after resetting
4. When the compressor starts after the fault of four way valve switching
The lower limit of frequency keeps A Hz for B seconds with any conditions 1 through 4 above.
3.3.4 3-minute Standby
Turning on the compressor is prohibited for 3 minutes after turning it off.
(The function is not activated when defrosting.)
3.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
(The function is not activated when defrosting.)
Cooling Heating
A (Hz) 68 66
B (seconds) 45
RK(X)S25/35E2V1B
RK(X)S25/35G2V1B
RK(X)S25/35G2V1B9
RXS25/35J2V1B
RXS25K3V1B
RXS35K2V1B
RXS25/35L2V1B
RXS25/35L3V1B
A (Hz) 48 40
B (Hz) 64 54
C (Hz) 88 72
D (seconds) 240 180
E (seconds) 360 420
F (seconds) 180 180
(sec.)
Time
(R13528)
(Hz)
Frequency
C
B
DEF
A

Table of Contents

Other manuals for Daikin RXS25K3V1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin RXS25K3V1B and is the answer not in the manual?

Daikin RXS25K3V1B Specifications

General IconGeneral
BrandDaikin
ModelRXS25K3V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals