20 | Electrical installation
Installer and user reference guide
108
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1D – 2023.02
A
B
C
b2
b3
c1
c2
b1
a
A Outdoor unit
B Indoor unit
C Central user interface (etc...)
a Main line
b1, b2, b3 Branch lines
c1, c2 No branch is allowed after branch
Example:
e
d
F1/F2
(16 V)
P1/P2
(16 V)
220-240 V
1~ 50 Hz
c
a
Y
V
b
220-240 V
1~ 50 Hz
380-415 V
3N~ 50 Hz
a Main switch
b Earth connection
c Power supply wiring (including earth) (EMC shielded cable)
F1/F2 Interconnection wiring (EMC shielded cable)
P1/P2 Remote controller wiring
V Outdoor unit (RXYSA4~6_V)
Y Outdoor unit (RXYSA4~6_Y)
d Indoor unit
e User interface
20.1.3 Guidelines when knocking out knockout holes
NOTICE
Precautions when making knockout holes:
â–ª Avoid damaging the casing.
â–ª After making the knockout holes, we recommend you remove the burrs and paint
the edges and areas around the edges using repair paint to prevent rusting.
â–ª When passing electrical wiring through the knockout holes, wrap the wiring with
protective tape to prevent damage.