22 | Configuration
Installer and user reference guide
126
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1D – 2023.02
1 Make sure the 7‑segment display indication is in the default situation (normal
operation).
2 Push BS1 one time.
Result: Mode1 is accessed:
3 Push BS2 10 times.
Result: Mode1 setting 10 is addressed:
4 Push BS3 one time; the value which is returned (depending on the actual field
situation), is the amount of indoor units which are connected to the system.
Result: Mode 1 setting 10 is addressed and selected, return value is
monitored information
5 To quit mode 1, push BS1 one time.
22.2.6 To use mode 2
The master unit should be used to input field settings in mode2.
Mode2 is used to set field settings of the outdoor unit and system.
What How
Changing and accessing the
setting in mode2
▪ Push BS1 for more than fiveseconds to select
mode2.
â–ª Push BS2 to select the required setting.
â–ª Push BS3 one time to access the selected
setting's value.
To quit and return to the initial
status
Push BS1.
Changing the value of the
selected setting in mode2
▪ Push BS1 for more than fiveseconds to select
mode2.
â–ª Push BS2 to select the required setting.
â–ª Push BS3 one time to access the selected
setting's value.
â–ª Push BS2 to select the required value of the
selected setting.
â–ª Push BS3 one time to validate the change.
â–ª Push BS3 again to start operation with the
chosen value.
Example:
Checking the content of parameter [2‑18] (to activate or deactivate the high static
pressure setting of the outdoor unit's fan).
[Mode‑Setting]=Value in this case is defined as: Mode=2; Setting=7; Value=the
value we want to know/change.
1 Make sure the 7‑segment display indication is in the default situation (normal
operation).
2 Push BS1 for more than five seconds.
Result: Mode2 is accessed: