20 | Electrical installation
Installer and user reference guide
111
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1D – 2023.02
20.1.5 About electrical compliance
This equipment complies with:
▪ EN/IEC 61000‑3‑12 provided that the short-circuit power S
sc
is greater than or
equal to the minimum S
sc
value at the interface point between the user's supply
and the public system.
- EN/IEC 61000‑3‑12 = European/International Technical Standard setting the
limits for harmonic currents produced by equipment connected to public low-
voltage systems with input current >16A and ≤75A per phase.
- It is the responsibility of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if necessary, that the
equipment is connected ONLY to a supply with a short-circuit power S
sc
greater
than or equal to the minimum S
sc
value.
Model Minimum S
sc
value
RXYSA4_V 122.95kVA
RXYSA5_V 154.07kVA
RXYSA6_V 173.05kVA
20.1.6 Specifications of standard wiring components
Component RXYSA*_V RXYSA*_Y
Power supply cable MCA
(a)
27.0A 13.6A
Voltage 220-240V 380-415V
Phase 1~ 3N~
Frequency 50Hz
Wire size MUST comply with national wiring
regulation.
3-core cable 5-core cable
Wire size based on the current, but not less
than:
4.0mm
2
2.5mm
2
Interconnection
cable (indoor ↔
outdoor)
Voltage 220-240V
Wire size Only use harmonised wire providing double
insulation and suitable for applicable
voltage.
2-core cable
0.75-1.5mm²
Recommended field fuse 32A, C curve 16A, C curve
Earth leakage circuit breaker /
residual current device
30mA – MUST comply with national wiring
regulation
(a)
MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of
combination with indoor units for exact values).