22 | Configuration
Installer and user reference guide
136
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1D – 2023.02
To activate this in… Change…
Heating operation [2‑42]=1.
This setting is used in conjunction with
setting [2‑9].
Eco
The original refrigerant temperature target, which is defined by the operation
method (see above) is kept without any correction, unless for protection control.
To activate this in… Change…
Cooling operation [2‑41]=0.
This setting is used in conjunction with
setting [2‑8].
Heating operation [2‑42]=0.
This setting is used in conjunction with
setting [2‑9].
22.3.3 Example: Automatic mode during cooling
A
B
E
100%
50%
T
e
C
D
3°C
6°C
35°C F
A Actual load curve
B Virtual load curve (initial capacity automatic mode)
C Virtual target value (initial evaporation temperature value automatic mode)
D Required evaporation temperature value
E Load factor
F Outside air temperature
T
e
Evaporating temperature