17 | Unit installation
Installer and user reference guide
78
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1D – 2023.02
(mm)
758
>150
(480-490)
485
4× M12
a
a Make sure not to cover the drain holes of the bottom plate of the unit.
INFORMATION
The recommended height of the upper protruding part of the bolts is 20mm.
20
NOTICE
Fix the outdoor unit to the foundation bolts using nuts with resin washers (a). If the
coating on the fastening area is stripped off, the metal can rust easily.
a
17.3.4 To install the outdoor unit
4× M12
17.3.5 To provide drainage
â–ª Make sure that condensation water can be evacuated properly.