16 | Special requirements for R32 units
Installer and user reference guide
64
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1D – 2023.02
NOT OK OK Case
4
a
d
b
B B
B
a
B B
d
b
a
d
b
A B
a
d
b
d
d
B B
B
a
B B
d
d
b
b
In case a ducted indoor unit is serving
a different room than where it is
installed, both supply and return air
MUST be directly ducted to that
room.
The room area and remote controller
rules MUST be followed only in the
served room when a given room is
served by only one ducted indoor unit
installed in a different room.
In all other situations both the room
where the ducted unit is installed and
the served room(s) need to follow the
room area and remote controller
rules.
A: No room area restrictions apply. No
remote controller required.
B: Room area restrictions apply, and
installation of remote controller
required.
5
a
d
d
b
a
d
d
b
In case of two R32 safety system
compatible remote controllers, at
least one remote controller should be
in the room of the indoor.
6
a
b b
d
a
b b b
d
Group control is allowed up to a
maximum of 5indoor units connected
to different ports or connected to the
same port. At least one R32 safety
system compatible remote controller
should be in the room of the indoors.
7
a
b
d
b
d
e
f
In particular situations it is mandatory
to install a remote controller at a
supervised location.
In room: master remote controller in
fully functional OR alarm only.
In supervisor room: supervisor remote
controller.
a Outdoor unit
b Indoor unit
c Remote controller NOT compatible with R32 safety system
d Remote controller compatible with R32 safety system
e Remote controller in supervisor mode
f Supervisor room
g Ducts (supply and return air)