16 | Special requirements for R32 units
Installer and user reference guide
70
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1D – 2023.02
Room
A B
Charge limit [kg] — 16.5
System charge limit [kg] 16.5
System charge [kg] 14.0
Judgement
a Outdoor unit
b Indoor unit
A/B Room A/B
Example4:
Room
A B
Area [m²] 8 20
Installation height [m] 2.5 2.5
Lowest underground floor — —
Other floors ● ●
Charge limit [kg] 6.0 12.7
System charge limit [kg] 6.0
System charge [kg] 12.0
Judgement
a Outdoor unit
b Indoor unit
A/B Room A/B