20 | Electrical installation
Installer and user reference guide
122
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752782-1A – 2024.02
20.1.5 About electrical compliance
This equipment complies with:
EN/IEC 61000‑3‑12 provided that the short-circuit power S
sc
is greater than or
equal to the minimum S
sc
value at the interface point between the user's supply
and the public system.
- EN/IEC 61000‑3‑12 = European/International Technical Standard setting the
limits for harmonic currents produced by equipment connected to public low-
voltage systems with input current >16A and ≤75A per phase.
- It is the responsibility of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if necessary, that the
equipment is connected ONLY to a supply with a short-circuit power S
sc
greater
than or equal to the minimum S
sc
value.
Model Minimum S
sc
value
RXYSA8 2684kVA
RXYSA10 3101kVA
RXYSA12 3383kVA