21 | Configuration
Installer and user reference guide
130
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752782-1A – 2024.02
Item Description
DIP switches By operating the DIP switches it is possible to:
DS1 (1): COOL/HEAT selector (refer to the manual of
the cool/heat selector switch). OFF=not
installed=factory setting
DS1 (2~4): NOT USED. DO NOT CHANGE THE FACTORY
SETTING.
DS2 (1~4): NOT USED. DO NOT CHANGE THE FACTORY
SETTING.
See also:
"21.1.2Field setting components"[4130]
Mode 1 and 2
Mode Description
Mode 1
(monitoring settings)
Mode1 can be used to monitor the current situation of
the outdoor unit. Some field setting contents can be
monitored as well.
Mode 2
(field settings)
Mode2 is used to change the field settings of the
system. Consulting the current field setting value and
changing the current field setting value is possible.
In general, normal operation can be resumed without
special intervention after changing field settings.
Some field settings are used for special operation (e.g.,
one time operation, recovery/vacuuming setting, manual
adding refrigerant setting, etc.). In such a case, it is
required to abort the special operation before normal
operation can restart. It will be indicated in below
explanations.
See also:
"21.1.3To access mode 1 or 2"[4131]
"21.1.4To use mode 1"[4132]
"21.1.5To use mode 2"[4132]
"21.1.6Mode 1: monitoring settings"[4133]
"21.1.7Mode 2: field settings"[4135]
21.1.2 Field setting components
Location of the 7‑segment displays, buttons and DIP switches:
a b
BS1 BS2
DS1 DS2
BS3
c
X27A
BS1 MODE: for changing the set mode
BS2 SET: for field setting
BS3 RETURN: for field setting
DS1, DS2 DIP switches
a 7-segment displays
b Push buttons