21 | Configuration
Installer and user reference guide
133
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752782-1A – 2024.02
What How
Changing the value of the
selected setting in mode2
Push BS1 for more than fiveseconds to select
mode2.
Push BS2 to select the required setting.
Push BS3 one time to access the selected
setting's value.
Push BS2 to select the required value of the
selected setting.
Push BS3 one time to validate the change.
Push BS3 again to start operation with the
chosen value.
Example:
Checking the content of parameter [2‑18] (to activate or deactivate the high static
pressure setting of the outdoor unit's fan).
[Mode‑Setting]=Value in this case is defined as: Mode=2; Setting=18; Value=the
value we want to know/change.
1 Make sure the 7‑segment display indication is in the default situation (normal
operation).
2 Push BS1 for more than five seconds.
Result: Mode2 is accessed:
3 Push BS2 18 times (or press and hold BS2 until the display reaches 18, then
release).
Result: Mode2 setting18 is addressed:
4 Push BS3 one time. The display shows the status of the setting (depending on
the actual field situation). In the case of [2‑18], the default value is "0", which
means the ventilated enclosure function is deactivated.
Result: Mode 2 setting 18 is addressed and selected, return value is the
current setting situation.
5 To change the value of the setting, push BS2 until the required value appears
on the 7‑segment display.
6 Push BS3 one time to validate the change.
7 Push BS3 to start operation according to the chosen setting.
8 Push BS1 one time to quit mode2.
21.1.6 Mode 1: monitoring settings
[1‑1]
Shows the status of low noise operation.
Low noise operation reduces the sound generated by the unit compared to
nominal operating conditions.
[1‑1] Description
0 Unit is currently not operating under low noise
restrictions.
1 Unit is currently operating under low noise restrictions.