21 | Configuration
Installer and user reference guide
133
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752782-1A – 2024.02
What How
Changing the value of the
selected setting in mode2
▪ Push BS1 for more than fiveseconds to select
mode2.
▪ Push BS2 to select the required setting.
▪ Push BS3 one time to access the selected
setting's value.
▪ Push BS2 to select the required value of the
selected setting.
▪ Push BS3 one time to validate the change.
▪ Push BS3 again to start operation with the
chosen value.
Example:
Checking the content of parameter [2‑18] (to activate or deactivate the high static
pressure setting of the outdoor unit's fan).
[Mode‑Setting]=Value in this case is defined as: Mode=2; Setting=18; Value=the
value we want to know/change.
1 Make sure the 7‑segment display indication is in the default situation (normal
operation).
2 Push BS1 for more than five seconds.
Result: Mode2 is accessed:
3 Push BS2 18 times (or press and hold BS2 until the display reaches 18, then
release).
Result: Mode2 setting18 is addressed:
4 Push BS3 one time. The display shows the status of the setting (depending on
the actual field situation). In the case of [2‑18], the default value is "0", which
means the ventilated enclosure function is deactivated.
Result: Mode 2 setting 18 is addressed and selected, return value is the
current setting situation.
5 To change the value of the setting, push BS2 until the required value appears
on the 7‑segment display.
6 Push BS3 one time to validate the change.
7 Push BS3 to start operation according to the chosen setting.
8 Push BS1 one time to quit mode2.
21.1.6 Mode 1: monitoring settings
[1‑1]
Shows the status of low noise operation.
Low noise operation reduces the sound generated by the unit compared to
nominal operating conditions.
[1‑1] Description
0 Unit is currently not operating under low noise
restrictions.
1 Unit is currently operating under low noise restrictions.