21 | Configuration
Installer and user reference guide
139
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752782-1A – 2024.02
[2‑35] Description
0 In case the outdoor unit is installed in the lowest
position (indoor units are installed on a higher position
than outdoor units) and the height difference between
the highest indoor unit and the outdoor unit exceeds
40m, the setting [2‑35] should be changed to 0.
1 (default)
Other changes/limitations to the circuit apply, for more information see
"18.1.7Refrigerant piping length and height difference"[492].
[2‑45]
SV unit shut-off valve setting.
[2‑45] Description
0 (default) Shut-off valve fully open
1 Shut-off valve fully closed
[2‑54]
Indoor unit connection setting.
[2‑54] Description
0 (default) Direct connection to the outdoor unit is not possible
1 Direct connection to the outdoor unit is allowed
[2‑60]
Supervisor remote controller setting. A power reset is required to save this setting.
For details about the supervisor remote controller, see "16.2 System layout
requirements" [4 61] or refer to the remote controller installation and user
reference guide.
[2‑60] Description
0 (default) No supervisor remote controller connected to the
system
1 Supervisor remote controller connected to system
[2‑81]
Cooling comfort setting.
This setting is used in conjunction with setting [2‑8].
[2‑81] Cooling comfort setting
0 Eco
1 (default) Mild
2 Quick
3 Powerful
For more information and advice about the impact of these settings, see
"21.2Energy saving and optimum operation"[4140].
[2‑82]
Heating comfort setting.
This setting is used in conjunction with setting [2‑9].