27 | Technical data
Installer and user reference guide
170
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752782-1A – 2024.02
Note: For better serviceability, use a distance ≥250mm for all dimensions marked
with 'a'.
Multiple rows of units ( )
b [mm]
H
B
≤½H
U
b≥250
½H
U
<H
B
≤H
U
b≥300
H
B
>H
U
H
B
H
U
≥1000
≥200
≥2000
≥100
≥3000
≥600
≥1500
b
≥100
≥100
≥100
≥100
≥100
≥100
H
B
H
U
Note: For better serviceability, use a side by side distance ≥250 mm (instead of
≥100mm as shown on the figures above).
Stacked units (max. 2 levels) ( )
A1
B1
A2
B2
A2
≥1000
A2
≥300
≥100
≥100
≥100
≥300
≥100
≥100
B2
≥100
≥1000
B2
A1=>A2 (A1) If there is danger of drainage dripping and freezing between the upper and
lower units…
(A2) Then install a roof between the upper and lower units. Install the upper unit
high enough above the lower unit to prevent ice buildup at the upper unit's bottom
plate.
B1=>B2 (B1) If there is no danger of drainage dripping and freezing between the upper and
lower units…
(B2) Then it is not required to install a roof, but seal the gap between the upper
and lower units to prevent discharged air from flowing back to the suction side
through the bottom of the unit.
Note: For better serviceability, use a side by side distance ≥250 mm (instead of
≥100mm as shown on the figures above).