Dimensions ED34-862
250 FXMQ-P
FXMQ50PVE
Unit (mm)
49
M4
For M10
5 × 150=750
16-8 × 12 oblong hole
18-8 × 12 oblong hole
30-φ 4.7 hole
7
4
11
6
52
1
3
12
9
8
10
1
2
3
4
5
6
7
8
9
10
11
12
(467 or less)
1000
60
(A case without
the ceiling)
Socket (For maintenance)
513
13 × 65=845
REMARK
Air suction flange
277
925
Drain hose (Accessory)
(Service space)
700 or more
27
(Service space)
40
PART NAME
245
or less
O. D. φ 32 (Outlet)
950
150
167
ITEM
631
785
Hook
φ 12.7 flale connection
Interunit wiring connection
Power supply connection
Liquid pipe connection
φ 6.4 flale connection
450 or more
247
Air discharge flange
(Suspention bolt position)
290
(All around)
232
Control box (Inside)
1038 (Suspention bolt position)
Adjustable
144
300 or more
28
200
150
212
Drain pipe connection
Ground terminal (Terminal in Control box)
VP25 (O. D. φ 32, I. D. φ 25)
(All around)
80
150
(Note. 4)
300
View
(All around)
300 or less
700 or less
169
6 × 150=900
165
805
VP25 (O. D. φ 32, I. D. φ 25)
760
(From the Air outlet)
11 × 65=715
59
3 × 65=195
215
700
2 × 65=130
Gas pipe connection
Floor surface
435
(All around)
Ceiling
36-φ 4.7 hole
Inspection hatch 450 or more
Air inlet
(Note. 2)
Air outlet
Air
outlet
Air inlet
(From the Air inlet)
CASE 1)
Control box
200
Inspection hatch 1
(450mm × 450mm)
or less
View B-2
Control box
CASE 2), 3)
Inspection hatch 1
(450mm × 450mm)
Control box
View B-1
20
Control box
B
or more
Ceiling
Inspection hatch
1300
(SAME AS THE INDOOR
UNIT SIZE +300 OR MORE)
Inspection hatch 3
700
or more
Fig. A
Inspection hatch Ceiling
Control box
or more
300
Unit base
Air
inlet
Air
outlet
or more
or more
700
Inspection hatch 2
(SAME AS THE INDOOR
UNIT SIZE OR MORE)
200
or more
or less
1000
Notes) 1. Location of MANUFACTURE'S LABEL:
Control box surface
2. Mount the air filter at the suction side.
Select its colorimethod (gravity method)
50% or more.
3. Do not locate things should not be wet
under the indoor unit.
Dews may drop when humidity reaches
over 80%, or a drain gets stuck, or air
filters are not clean.
4. Space for Service Works
1) One inspection hatch (450 × 450) on the control box
side and a space of 300mm or more under the unit.
(Fig. A)
2) One inspection hatch (450 × 450) on the control box
side and 2 (two) inspection hatches under the unit.
(Arrow View B-1)
3) 3 (three) inspection hatches under the unit and the
control box. (Arrow View B-2)
According to any one of below 1)~3), secure a space
for service works, such as, checking and maintenance
of control box and drain pumps, etc.
2500 or more
3D060159D