ED34-862 Dimensions
FXMQ-P 251
7
FXMQ63P / 80PVE
Unit (mm)
6 × 150=900
513
18-8 × 12 oblong hole
16-8 × 12 oblong hole
36-φ 4.7 hole
30-φ 4.7 hole
9
8
10
7
4
11
6
5
1
3
12
28290
(All around)
27 631
1038 (Suspention bolt position)
212
150
700
300 or less
80
300
1000
150
2500 or more
(A case without
the ceiling)
805
950
5 × 150=750
785
760
2
169
40
View
925
49
277
232
300 or more
(All around)
(Note. 4)
150
247
11 × 65=715
3 × 65=195
(Service space)
700 or more
(From the Air outlet)
(All around)
165
13 × 65=845
700 or less
2 × 65=130
65
59
167
215
245
200
or less
(Suspention bolt position)
144
(467 or less)
Adjustable
Air inlet
(Note. 2)
Air outlet
Floor surface
Inspection hatch 450 or more
Air inlet
(All around)
(From the Air inlet)
Ceiling
435
Air
outlet
View B-1
Control box
Inspection hatch 1
(450mm × 450mm)
or less
Inspection hatch 1
(450mm × 450mm)
200
Control box
CASE 1)
Inspection hatch Ceiling
Control box
Fig. A
View B-2
Control box
CASE 2), 3)
or more
700
or more
or more
1000
200
or less
Inspection hatch 2
(SAME AS THE INDOOR
UNIT SIZE OR MORE)
B
20
Ceiling
Control box
Inspection hatch
(SAME AS THE INDOOR
UNIT SIZE +300 OR MORE)
Inspection hatch 3
1300
700
or more
Air
outlet
Air
inlet
Unit base
or more
300
(Service space)
450 or more
or more
Notes) 1. Location of MANUFACTURE'S LABEL:
Control box surface
2. Mount the air filter at the suction side.
Select its colorimethod (gravity method)
50% or more.
3. Do not locate things should not be wet
under the indoor unit.
Dews may drop when humidity reaches
over 80%, or a drain gets stuck, or air
filters are not clean.
4. Space for Service Works
1) One inspection hatch (450 × 450) on the control box
side and a space of 300mm or more under the unit.
(Fig. A)
2) One inspection hatch (450 × 450) on the control box
side and 2 (two) inspection hatches under the unit.
(Arrow View B-1)
3) 3 (three) inspection hatches under the unit and the
control box. (Arrow View B-2)
According to any one of below 1)~3), secure a space
for service works, such as, checking and maintenance
of control box and drain pumps, etc.
M4
For M10
1
2
3
4
5
6
7
8
9
10
11
12
Socket (For maintenance)
REMARK
Air suction flange
Drain hose (Accessory)
PART NAME
O. D. φ 32 (Outlet)
ITEM
Hook
φ 15.9 flale connection
Interunit wiring connection
Power supply connection
Liquid pipe connection
φ 9.5 flale connection
Air discharge flange
Control box (Inside)
Drain pipe connection
Ground terminal (Terminal in Control box)
VP25 (O. D. φ 32, I. D. φ 25)
VP25 (O. D. φ 32, I. D. φ 25)
Gas pipe connection
3D060161E